Engineering offices

On this page, you can download ready-to-use diagrams and work explanations to support your design, or log in to the Suunnittelukone design tool to create building-specific diagrams.

We recommend leaving a distance equal to at least five times the DN size of the water meter between the main line and the meter. This means, for example, not fitting a hot water tee within 75 mm of a DN15 water meter. The safe distance from a DN20 water meter would be 100 mm. There is no issue with placing a ball valve, a dirt trap or an elbow right in front of the fitting, however. The safe distance is designed to ensure that meter readings are not affected by flow in the main line.

HYDROLINK Air

Design instructions for water metering systems

Work explanation

HYDROLINK Air (PDF)

Work explanation

HYDROLINK Air (DOCX)

Design instructions

HYDROLINK Air (PDF)

Design instructions

HYDROLINK Air (DWG)

Work explanation

Hydrolink Line AD-X (PDF)

Work explanation

Hydrolink Line (DOCX)

Design instructions

Hydrolink Line (PDF)

Design instructions

Hydrolink Line (DWG)

Work explanation

Hydrolink Line (DWG)

Work explanation

Hydrolink Line AD-X (DOCX)

Design instructions

Hydrolink Line AD-X (PDF)

Design instructions

Hydrolink Line AD-X (DWG)

Work explanation

Hydrolink Wireless (PDF)

Work explanation

Hydrolink Wireless (DOCX)

Design instructions

Hydrolink Wireless (PDF)

Design instructions

Hydrolink Wireless (DWG)